A244 DRIVEFLEX® Control Pair(s)

LUTZE Driveflex A244
Application
  • Twisted shielded pair cable for VFD & Motor applications to
  • transmit control signals from drives to motors
  • Cable design for harsh industrial environments and operating
  • conditions with high noise levels
  • XLPE insulation with low capacitance
  • TC-ER for use with cable trays without conduit and
  • alongside power cables
  • Separating control from power allows full ampacity rating of
  • the power cable
  • Compliant with NFPA 79 for wiring of industrial
  • machinery
  • WTTC – wind turbine tray cable rating for use in wind power
  • generation
  • Dry, damp or wet conditions
Characteristics
  • Flexible XLPE conductor design
  • Non-wicking fillers
  • Effective dual layer shield for EMC compliance
  • Specially formulated jacket for oil resistance and easy strip
  • design
  • Low capacitance cable
  • Sunlight resistant
  • Direct burial
  • Talc and Silicone free
Part number Description No. of conductors incl. ground OD - Ø ca. mm OD - Ø ca. inches Weight Lbs/Mft Copper Lbs/Mft
A2441802 AWG 18 (16/30)
1 TSP AWG 18 (16/30)
1 pair
8.7 0.344 77 29
A2441602 AWG 16 (26/30)
1 TSP AWG 16 (26/30)
1 pair
9.4 0.370 88 36
A2441402 AWG 14 (41/30)
1 TSP AWG 14 (41/30)
1 pair
10.2 0.400 108 51
A2441804 AWG 18 (16/30)
2 TSP AWG 18 (16/30)
2 pairs
14.0 0.550 164 58
A2441604 AWG 16 (26/30)
2 TSP AWG 16 (26/30)
2 pairs
15.5 0.610 189 73
A2441404 AWG 14 (41/30)
2 TSP AWG 14 (41/30)
2 pairs
16.6 0.655 237 102
Voltage: 600V UL TC-ER
1000V Flexible VFD Servo Cable
1000V WTTC, 1000V 105C AWM
Temperature: -40°C - +90°C static
Bending radius: 6 x cable OD
Conductor marking: Black with white number print
Oil resistance: Oil Res II
Approvals: UL Type “Flexible Motor Supply
Cable (Flexible VFD Servo
Cable)”
UL Type TC-ER
UL/CE
WTTC
Class I, II Div. 2 per NEC
Art. 336, 392, 501, 502
AWM 20886
c(UL) TC
CIC FT4
UL 1277
Wet/Dry
RoHS
REACH
Construction: AWG conductor
Flexible fine wire stranded tinned copper conductors for
improved electrical characteristics and reduced oxidation
XLPE insulation XHHW-2, Wet/Dry
Each pair shielded with foil tape, drain wire, tinned copper
braid (≥ 80% optical coverage), then wrapped in clear foil
Oil resistant PVC jacket
Black jacket RAL 9005